Heating storage tank PBM-R (with bottom heat exchanger), 300L - 2000L
The PBM-R storage tank allows you to store the heat generated by the boiler. It ensures optimal operation of biomass (or solid fuel) boilers. This allows it to operate at nominal capacity even when the heating system does not require all of the heat energy it produces. The heat produced is accumulated and stored in the tank and can be used even when the boiler itself has cooled down.
The storage tank version with a single heating exchanger allows you to connect an additional heating source with a separate heat carrier, such as a solar collector system.
As an optional extra - removable insulation with a thickness of 100 mm and an outer cover made of PVC, color RAL 9006. Insulation types available for all models: soft PU, fleece. Please contact us for information on insulation availability.
Main product features:
- Multiple temperature sensor installation locations.
- Primed tank exterior.
- All threads are internal.
- Inlet/outlet connections at a 90° angle, which makes installation easier and more versatile (the boiler can be installed in the corner of the boiler room).
- Additional heating heat exchanger.
- Easy installation.
See the image gallery for a diagram of the tank sizes.
PBM-R 300 | PBM-R 500 | PBM-R 800 | PBM-R 1000 | PBM-R 1500 | PBM-R 2000 | ||
Capacity | L | 300 | 500 | 800 | 1000 | 1500 | 2000 |
Height without insulation / with insulation | H, Hi, mm | 1410/1460 | 1700/1750 | 1838/1888 | 2039/2089 | 2140/2290 | 2131/2181 |
Mounting height | mm | 1430 | 1727 | 1877 | 2073 | 2192 | 2220 |
Diameter without insulation /with insulation | D, mm | Ø 550/750 | Ø 650/850 | Ø 790/990 | Ø 790/990 | Ø 1000/1200 | Ø 1200/1400 |
Operating pressure/Max. buffer temperature | bar/0C | 3-95 | 3-95 | 3-95 | 3-95 | 3-95 | 3-95 |
Operating pressure /Max. coil temperature | bar/0C | 16/110 | 16/110 | 16/110 | 16/110 | 16/110 | 16/110 |
Recommended boiler size, connected to buffer tank | kW | 06-10 | 10-17 | 15-27 | 18-33 | 27-50 | 36-67 |
Weight without insulation/with insulation | kg, kg i | 75/85 | 106/118 | 144/161 | 164/182 | 257/280 | 329/356 |
Sleeve for Electric heating element | В, mm, Rp 11/2” | 860 | 997 | 1090 | 1260 | 1260 | 1308 |
Heat carrier | С1, mm, Rp11/2” | 240 | 239 | 290 | 290 | 339 | 388 |
Heat carrier | С2, mm, Rp11/2” | 240 | 239 | 290 | 290 | 339 | 388 |
Heat carrier | С3, mm, Rp11/2” | 550 | 643 | 710 | 775 | 833 | 848 |
Heat carrier | С4, mm, Rp11/2” | 550 | 643 | 710 | 775 | 833 | 848 |
Heat carrier | С5, mm, Rp11/2” | 860 | 997 | 1090 | 1260 | 1327 | 1308 |
Heat carrier | С6, mm, Rp11/2” | 860 | 997 | 1090 | 1260 | 1327 | 1308 |
Heat carrier | С7, mm, Rp11/2” | 1170 | 1451 | 1750 | 1750 | 1821 | 1768 |
Heat carrier | С8, mm, Rp11/2” | 1170 | 1451 | 1750 | 1750 | 1821 | 1768 |
Sensor sleeve | А1, mm, Rp1/2” | 240 | 239 | 290 | 290 | 339 | 388 |
Sensor sleeve | А2, mm, Rp1/2” | 550 | 643 | 710 | 775 | 833 | 848 |
Sensor sleeve | А3, mm, Rp1/2” | 860 | 997 | 1090 | 1260 | 1327 | 1308 |
Sensor sleeve | А4, mm, Rp1/2” | 1170 | 1451 | 1750 | 1750 | 1821 | 1768 |
Air vent | F, mm, Rp11/2” | 1410 | 1700 | 2039 | 2039 | 2140 | 2131 |
Coil capacity S1 | S1 L | 5,6 | 9,8 | 14 | 15,2 | 20,65 | 30 |
Heat exchange surface S1 | S1 m2 | 0,9 | 1,6 | 2,3 | 2,48 | 3,4 | 4,9 |
Inlet/Outlet Lower coil S1 | S1i/S1o, mm, Rp1” | 640/240 | 689/239 | 785/290 | 830/290 | 939/339 | 1158/388 |